🧰 What Is Insulation Resistance Testing?
Insulation Resistance (IR) testing is a fundamental, non-destructive diagnostic method used to assess the quality of electrical insulation. This is commonly performed on cables, transformers, motors, and switchgear. A megohmmeter (or “megger”) applies a high DC voltage to measure leakage current, which is used to calculate resistance (R = V/I). High resistance values indicate healthy insulation.
🎯 Why It Matters for Predictive Maintenance
Predictive maintenance aims to detect equipment issues before failure occurs. Insulation resistance testing is an essential tool in this effort. Benefits include:
- Early detection of moisture, dirt, or thermal degradation
- Improved equipment reliability and uptime
- Reduced risk of electric shock or arc faults
- Compliance with NETA, IEEE, and IEC testing standards
IR tests are cost-effective and provide meaningful data trends when logged over time.
🛠️ Equipment Used
- Megohmmeters (500V, 1000V, 2.5kV, 5kV, or 10kV models)
- Guard, line, and earth terminals for precision
- Timed testing features and PI/DA calculations
Image:

📝 Step-by-Step Testing Procedure
- Safety First: De-energize and verify equipment is isolated.
- Connect Tester: Use the L (line) lead to the conductor, E (earth) to ground, and G (guard) if applicable.
- Set Voltage: Common values:
- 500V for control wiring
- 1000V for 480V systems
- 2.5kV–5kV for transformers/motors
- Take Readings: Spot reading at 1 min; calculate PI = 10-min/1-min value
- Interpret Results: Refer to NETA/IEEE standards for acceptable values.
Image:
📊 Interpreting Results
PI Value | Insulation Condition |
---|---|
> 2.0 | Excellent |
1.5–2.0 | Acceptable |
< 1.25 | Investigate |
Adjust for environmental factors like humidity and temperature. Log and trend results to track insulation deterioration over time.
✅ Applications by Equipment Type
Equipment | Voltage Applied | Test Points |
Motors | 500–1000V | Windings to frame |
Transformers | 1–5kV | HV & LV windings to ground |
Cables | 1–5kV | Conductor to sheath/ground |
Switchgear | 1–5kV | Bus to ground, phase-to-phase |
Image:
🛡️ Safety & Best Practices
- Lock-out/tag-out all circuits
- Use proper PPE for high-voltage testing
- Clean terminals and inspect for moisture
- Document and trend all results